INSPECTION PERFORMED BY

INSPECTOR:

Gregg Traum

Licensed General Contractor

Licensed Roofing Contractor

Lic# 847269

SPCB Lic# OPR8053

Real Estate Agt BRE #01474404

CONTACT:
20432 Alcalde
Ste D
Laguna Hills, Ca 92653
949.413.3650 Cell
888.202.4642 Office
email: youroneinspector@gmail.com
www.1stchoicepropertyinspections.net

REPORT INFORMATION
PREPARED FOR:
Jim Shoe

PROPERTY ADDRESS:
10 Portalon, Ladera Ranch, Ca 92694

 

Date: 12/8/2015 Time: 11:00 AM Report ID: 15-6051
Property:
10 Portalon
Ladera Ranch Ca 92694
Customer:
Jim Shoe

Real Estate Professional:

Joe Realtor
ABC Realty


Comment Key or Definitions

The following definitions of comment descriptions represent this inspection report. Any recommendations by the inspector to repair or replace suggests a further inspection by a qualified tradesperson.

In no way should this inspection and/or report be construed as a guarantee or warranty against structural / component / item defects or failure, presently or in the future. No expressed or implied guarantees/warranties are or were given.

Inspections are not performed to determine if additions and/or improvements are permitted. It is recommended that any concerns regarding building permits be directed to the owner and/or the city/county building department.

We certify that our inspector has no interest, present or contemplated, in this property or it's improvements and we have no involvement with tradespeople derived from any sales or improvements.

You may view and print your report by visiting the web site at: www.1stChoicePropertyInspections.net .

Comments highlighted in "RED" print requires attention due to defects, conditions or safety issues.

Digital photos may not be provided for every concern or defect. NOT ALL DEFECTS OR CONCERNS ARE PHOTOGRAPHED.

Inspected (IN) = Visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.

Not Inspected  (NI) = Did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.

Not Present  (NP) = This item, component or unit is not present in this structure.

Repair or Replace  (R/R) = The item, component or unit is not functioning as intended or needs further inspection by a qualified tradesperson. Items, components or units that can be repaired to satisfactory condition may not need replacement.

Safety Item (S) =  The item, component and/or unit does not conform to today's modern safety standards. Item, component and/or unit may function as intended, however does not provide modern safety characteristics, or may be missing and/or malfunctioning: Recommend repair or improvement

Maintenance or Informational  (M/I) = Comments and/or recommendations are for maintenance or informational purposes only.

It is highly recommended that the CLIENT attend the inspection so that they may be briefed on any findings so that there are no misinterpretations of this report. It is suggested that all interested parties thoroughly read the "General Summary" section of this report as well as it's entirety.

This inspection and report is intended solely for the client. Any reproduction or forwarding of this report to third parties without the express written consent of the client is prohibited.

Homes constructed prior to 1978 pose the possibility of Lead Paint. This is to be considered notice to client(s) and interested parties to this inspection report, that a Lead Paint inspection WAS NOT PERFORMED. If the client and/or interested parties to this inspection report are concerned with the possibility of Lead Paint contamination, we suggest a further evaluation by a tradesman qualified in that field. This notice shall hold 1st Choice Property Inspections, it's owner(s), officer(s) and vested partner(s), if any, harmless of any such Lead Paint conditions, or health issues if any exist.

Inspector:
Gregg Traum

Style of Home:
MULTI LEVEL SINGLE FAMILY

Occupancy Status:
FURNISHED & OCCUPIED

Estimated Age Of Home:
Approximatly 5-8 years

Area:
SUBURB

Viewed From:
STREET

Main Entrance Faces:
WEST

Persons Present:
BUYER, SELLER, SELLING AGENT

Weather:
HOT & HUMID

Approximate Temperature:
Over 80

Rain in last 3 days:
NO

 

Table of Contents

Summary

 

1st Choice Property Inspections

20432 Alcalde
Ste D
Laguna Hills, Ca 92653
949.413.3650 Cell
888.202.4642 Office
email: youroneinspector@gmail.com
www.1stchoicepropertyinspections.net

Inspection Date:12/8/2015

Customer
Jim Shoe

Property Address
10 Portalon
Ladera Ranch Ca 92694

The following items or discoveries indicate that these systems and/or components do not function as intended or adversely effect the habitability of the dwelling; or appear to warrant further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition, or recommendations to upgrade or enhance the function of the dwelling. This summary "Is Not" the entire report. The complete report may include additional information of concern to the client. It is recommended that the client read this report in it's entirety.

               

1.  Kitchen and Components
General Summary
1.6   RANGE VENT HOOD OPERATION
 Repair or Replace
Missing control knob
1.6 Item 1(Picture)
 
1.9   CABINETS
 Repair or Replace
Damaged sink shelf. Recommend the appropriate tradesman to correct
1.9 Item 1(Picture)
 

2(A).  Living Room
General Summary
2.5.A   ELECTRICAL / OUTLETS / SWITCHES
 Repair or Replace
Inoperable ceiling light, possible bulb
2.5.A Item 1(Picture)
 

2(D).  Master Bedroom
General Summary
2.1.D   WALLS
 Repair or Replace
Settlement cracking at the drywall
2.1.D Item 1(Picture)
 

2(E).  Hallway/Other
General Summary
2.7.E   SMOKE/CARBON MONOXIDE DETECTOR(S)
 Repair or Replace, Safety
As of May 2010, A Carbon Monoxide device is now mandatory by state law (SB 183) for human occupied dwellings and must be a certified device by the State Fire Marshall, preferred locations are outside of all sleeping areas and hallways at all levels of structure. Combined Smoke /Carbon Monoxide detectors are acceptable, providing the carbon monoxide detector emits an audible sound different than the smoke detector. Battery powered , Plug In, or Hard Wired (with a battery back-up) detectors are acceptable.Battery life must be a minimum of a 5 year life span. The lack of such a device is a Safety Issue. Location should not be any higher than 5' from floor level.

2(G).  Casitas
General Summary
2.3.G   DOORS (Representative Number)
 Repair or Replace
Missing door stops, wall damage may occur.
2.7.G   SMOKE/CARBON MONOXIDE DETECTOR(S)
 Repair or Replace, Safety
Carbon Monoxide detector is required.

3(A).  Master Bath
General Summary
3.0.A   SINK(S) (Including Plumbing)
 Repair or Replace
(1) Plumbing leak under the sink, Right sink
3.0.A Item 1(Picture)
 
(2) Loose/broken Hot water handle, Left sink
3.0.A Item 2(Picture)
 
(3) Sink stopper is inoperable, Left sink
3.0.A Item 3(Picture)
 
3.5.A   TUB(S)(including plumbing)
 Repair or Replace
Tub drains slow
3.8.A   WALLS
 Repair or Replace
Settlement cracking, wall of the toilet area
3.8.A Item 1(Picture)
 

3(B).  Private Bath, Hall Bedroom
General Summary
3.0.B   SINK(S) (Including Plumbing)
 Repair or Replace
Sink drains slow and stopper is inoperable. Possible clogged drain
3.0.B Item 1(Picture)
 
3.3.B   TOILET(S)(including plumbing)
 Repair or Replace
Corrosion at the angle stop valve, recommend replacement.
3.3.B Item 1(Picture)
 

3(D).  Casitas Bath
General Summary
3.5.D   TUB(S)(including plumbing)
 Repair or Replace
Missing tub drain stopper
3.5.D Item 1(Picture)
 

4.  Laundry Area
General Summary
4.2   ELECTRICAL
 Repair or Replace, Safety
No Ground Fault Circuit Interrupters near the Washing machine or Service sink (Where Applicable). Recommend GFCI (ground fault circuit interrupter) outlets within 6 feet of a water source. Safety issue.
4.2 Item 1(Picture)
 
4.9   DOOR(S)
 Repair or Replace
Missing the door stop, wall damage may occur.
4.9 Item 1(Picture)
 

5.  Garage
General Summary
5.8   MISCELLANEOUS
 Not Inspected
The structure is constructed with a residential fire sprinkler system, which is outside the scope of a home inspection. It is recommended to have the system tested/inspected upon move in and yearly beyond then 
5.8 Item 1(Picture)
 

7.  Exterior Components
General Summary
7.1   EXTERIOR WALL COVERING, FLASHING AND TRIM
 Repair or Replace
(1) Settlement cracking at the exterior stucco, recommend to seal areas to prevent moisture intrusion
7.1 Item 1(Picture)
7.1 Item 2(Picture)
 
(2) Exterior grade level is too high. Recommend to adjust the height of the exterior grade level to 3"-4" below stucco weep screed and/or foundation footing and close sprinkler heads.
7.1 Item 3(Picture)
7.1 Item 4(Picture)
 
7.5   DECKS, BALCONIES, STEPS, PORCHES, PATIO COVER(S) AND APPLICABLE RAILINGS
 Repair or Replace
Peeling paint at the railings, recommend to prep and paint
7.5 Item 1(Picture)
7.5 Item 2(Picture)
 
7.6   DRIVEWAY, WALKWAY(S), PATIO SLAB(S), STOOP(S)
 Repair or Replace
Lifting walkway slabs
7.6 Item 1(Picture)
 
7.8   LANDSCAPING, GRADING, DRAINAGE (Excluding Irrigation System)
 Repair or Replace
(1) Front fountain is inoperable
7.8 Item 1(Picture)
 
(2) Missing drain cap
7.8 Item 2(Picture)
 

8.  Plumbing System
General Summary
8.2   GAS SUPPLY (Where Applicable)
 Repair or Replace
Although it may not have been plumbing code when the hot water heater was installed, a gas line sediment trap on the gas line prior to the appliance is recommended. This is recommended to protect the water heater system and prolong the life span of the component. A gas line sediment trap shall be provided on the gas line downstream of the shut off valve and as close to the inlet of the equipment as practical. CA PLUMBING CODE 1212.8. Recommend repairs by a licensed tradesman.
8.2 Item 1(Picture)
8.2 Item 2(Picture)
 
8.5   WATER PRESSURE AT HOSE CONNECTION
 Repair or Replace
Water pressure is low. Optimum pressure is between 60-80 P.S.I. Recommend to contact the water municipal for a further inspection
8.5 Item 1(Picture)
 
8.6   MAIN WATER SHUT-OFF (Location / Condition)
 Maintenance/Information
The main shut off is the yellow lever located in garage. This is for your information. These controls are not turned or operated as to not to disturb the natural seating.
8.6 Item 1(Picture)
 
8.7   MISCELLANEOUS
 Not Inspected, Repair or Replace
(1) Recommend a catch/drain pan with a drain under the hot water heater
8.7 Item 1(Picture)
 
(2) Water softener system was not inspected. Interested parties may want to inquire with the supplier of the equipment.
8.7 Item 2(Picture)
 
(3) Drain line for the water softener has been pierced thru the stucco
8.7 Item 3(Picture)
8.7 Item 4(Picture)
 

9.  Heating
General Summary
9.0   HEATING EQUIPMENT
 Repair or Replace
No response from the Casitas furnace unit when tested. Recommend a further inspection by a HVAC Contractor
9.4   FILTRATION
 Repair or Replace
Improper size filter
9.4 Item 1(Picture)
9.4 Item 2(Picture)
 
9.8   FIREPLACE(S)
 Repair or Replace
(1) Gas line should be of a flexible Rigid material to prevent breakage in case of an earthquake.
9.8 Item 1(Picture)
9.8 Item 2(Picture)
 
(2) Broken handle at the fireplace screen, Family Room
9.8 Item 3(Picture)
 

12.  Roof System, Drainage, Roof Penetrations
General Summary
12.0   ROOF COVERINGS
 Repair or Replace, Maintenance/Information
(1) Tree limbs that are in contact with roof or hanging near roof should be trimmed back a minimum of 3 feet from the roof.
12.0 Item 1(Picture)
12.0 Item 2(Picture)
 
(2) The inspector did not walk upon the roof due to it's fragile nature. Roof covering was inspected from visible points, ground, windows, ladders, etc. Any further concerns from the client should be directed to a licensed roofer. Walking upon the roof by the inspector will have to be performed at the current owners' request and a signed waiver of liability against potential damage must be signed prior to for authorization.

13.  Swimming Pools and Equipment
General Summary
13.2   COPING
 Repair or Replace
Seepage at the spa coping
13.2 Item 1(Picture)
 
13.4   OPERATIONAL CONDITION OF POOL/SPA
 Repair or Replace
(1) Pool Pilot Salt maker Service light is flashing, recommend a further review by a pool technician
13.4 Item 1(Picture)
 
(2) Water feature is inoperable possibly due to an inoperable GFCI outlet
13.4 Item 2(Picture)
13.4 Item 3(Picture)
 
(3) Missing spa jets
13.4 Item 4(Picture)
 
13.7   LIGHTING (Pool/Spa)
 Repair or Replace
Pool/spa lighting is inoperable
13.7 Item 1(Picture)
13.7 Item 2(Picture)
 
13.8   ELECTRICAL
 Repair or Replace
Inoperable GFCI outlet, no power
13.8 Item 1(Picture)
 
13.9   SAFETY EQUIPMENT
 Repair or Replace
Right side wood gate does not automatically close which is required for child safety reasons
13.9 Item 1(Picture)
 


Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Gregg Traum

1.  Kitchen and Components

No opinion is offered as to the adequacy of dishwasher operation. Ovens, self or continuous cleaning operations, cooking functions, clocks, timing devices, lights and thermostatically controlled devices are not inspected for accuracy during this inspection. No warranty or guarantee is issued or implied.

Maytag Corp. issued a recall of 7.1 million dishwashers sold under the MAYTAG, AMANA, JENN-AIR, ADMIRAL, MAGIC CHEF, PERFORMA by Maytag, and CROSLEY brands after reports of fires starting due to electrical problems with the heating elements as reported by the U.S. Consumer Product Safety Commission in June 2010.

All the recalled dishwashers have plastic interiors and were sold nation wide between February 2006 thru April 2010 for between $250 & $900. They came in either black, bisque, white, silver or stainless front panels.

To determine if you have one of these recalled dishwashers, look for the model and serial numbers on the Left side of the door opening.

The recalled machines will have serial numbers starting with any of the following:

NW39, NW40, NW41, NW42, NW43, NW44, NW45, NW46, NW47, NW48, NW49, NW50, NW51, NY01, NY02, NY03, NY04, NY05, NY06, NY07, NY08, NY09, NY10, NY11, NY12, NY13, NY14, NY15, NY16, NY17, NY18, NY19 or Ending with any of the following: JC, JE, JG, JJ, JL, JN, JP, JR, JT, JV, JX, LA, LC, LE, LG, LJ, LL, LN, LP, LT, LV, LX, NA, NC, NE, NG, NJ, NL, NN, NP, NR.

If you have one of these dishwashers, you are urged to stop using it immediately and disconnect the power supply by either shutting off it's circuit breaker or by pulling out it's fuse.

Maytag will repair the recalled machines in-house or provide a rebate if a consumer decided to buy certain new models with stainless steel interiors. To schedule a repair or get a rebate, call MAYTAG @ 1-800-544-5513 or go to the company's recall site.

Styles & Materials
KITCHEN SINK:
STAINLESS STEEL
COUNTERTOP:
GRANITE
RANGE/COOK TOP:
GAS WITH ELECTRIC IGNITION
DISHWASHER:
APPEARS SERVICABLE
EXHAUST / RANGE HOOD:
VENTED
BUILT-IN MICROWAVE:
APPEARS SERVICABLE
FLOOR COVERING:
CERAMIC
   
    IN NI R/R S M/I NP
1.0 KITCHEN SINK (Type)          
1.1 PLUMBING (Including Fixtures)          
1.2 FOOD WASTE DISPOSER          
1.3 ELECTRICAL (Outlets / Wall Switches / Fixtures)          
1.4 DISHWASHER OPERATION          
1.5 RANGE(S) / COOKTOP(S) OPERATION          
1.6 RANGE VENT HOOD OPERATION          
1.7 MICROWAVE COOKING EQUIPMENT          
1.8 COUNTER TOPS          
1.9 CABINETS          
1.10 CEILINGS          
1.11 WALLS          
1.12 FLOORS          
1.13 WINDOWS (Representative Number)          
1.14 MISC.          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

Comments:

1.6  Missing control knob
1.9   Damaged sink shelf. Recommend the appropriate tradesman to correct

In homes built to comply with the National Building Code (The Code), GFCI protection is required for most outdoor receptacles, since 1973, bathroom receptacles, since 1975, garage wall outlets, since 1978, kitchen receptacles, since 1987, and all receptacles in crawl spaces and unfinished basements, since 1990. Owners of homes that do not have GFCIs installed in all critical areas specified in the latest version of the Code, should consider having them installed.

2(A) .  Living Room

The inspector shall observe: Walls, ceiling, and floors; steps, stairways, balconies, and railings; and a representative number of doors and windows. The inspector shall: Operate a representative number of windows and interior doors; and report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; carpeting; or draperies, blinds, or other window treatments. As a general rule, cosmetic deficiencies are considered normal wear and tear and not reported. Determining the condition of insulated glass windows is not always possible due to temperature, weather and lighting conditions. It is advisable to check with the owner(s) for any additional information.
Styles & Materials
CEILING MATERIAL:
DRYWALL
OPEN BEAM
and
WALL MATERIAL:
DRYWALL
FLOOR COVERING(S):
CERAMIC
DOOR(S):
FRENCH DOORS
WINDOW TYPES:
DUAL PANE INSULATED
 
    IN NI R/R S M/I NP
2.0.A CEILINGS          
2.1.A WALLS          
2.2.A FLOORS          
2.3.A DOORS (Representative Number)          
2.4.A WINDOWS (Representative Number)          
2.5.A ELECTRICAL / OUTLETS / SWITCHES          
2.6.A MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

Comments:

2.5.A   Inoperable ceiling light, possible bulb
The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area rugs or areas obstructed from view. Please be aware that the inspector has your best interest in mind. It is recommended that qualified contractors be used in your further repair issues as it relates to the comments in this inspection report.

2(B) .  Family Room

The inspector shall observe: Walls, ceiling, and floors; steps, stairways, balconies, and railings; and a representative number of doors and windows. The inspector shall: Operate a representative number of windows and interior doors; and report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; carpeting; or draperies, blinds, or other window treatments. As a general rule, cosmetic deficiencies are considered normal wear and tear and not reported. Determining the condition of insulated glass windows is not always possible due to temperature, weather and lighting conditions. It is advisable to check with the owner(s) for any additional information.
Styles & Materials
CEILING MATERIAL:
DRYWALL
WALL MATERIAL:
DRYWALL
FLOOR COVERING(S):
CERAMIC
DOOR(S):
FRENCH DOORS
WINDOW TYPES:
DUAL PANE INSULATED
 
    IN NI R/R S M/I NP
2.0.B CEILINGS          
2.1.B WALLS          
2.2.B FLOORS          
2.3.B DOORS (Representative Number)          
2.4.B WINDOWS (Representative Number)          
2.5.B ELECTRICAL / OUTLETS / SWITCHES          
2.6.B MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area rugs or areas obstructed from view. Please be aware that the inspector has your best interest in mind. It is recommended that qualified contractors be used in your further repair issues as it relates to the comments in this inspection report.

2(C) .  Bedroom(s)

The inspector shall observe: Walls, ceiling, and floors; steps, stairways, balconies, and railings; and a representative number of doors and windows. The inspector shall: Operate a representative number of windows and interior doors; and report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; carpeting; or draperies, blinds, or other window treatments. As a general rule, cosmetic deficiencies are considered normal wear and tear and not reported. Determining the condition of insulated glass windows is not always possible due to temperature, weather and lighting conditions. It is advisable to check with the owner(s) for any additional information.
Styles & Materials
CEILING MATERIAL:
DRYWALL
WALL MATERIAL:
DRYWALL
FLOOR COVERING(S):
CARPET
DOOR(S):
HOLLOW CORE
RAISED PANEL
WINDOW TYPES:
DUAL PANE INSULATED
 
    IN NI R/R S M/I NP
2.0.C CEILINGS          
2.1.C WALLS          
2.2.C FLOORS          
2.3.C DOORS (Representative Number)          
2.4.C WINDOWS (Representative Number)          
2.5.C ELECTRICAL / OUTLETS / SWITCHES          
2.6.C CLOSET(S)          
2.7.C SMOKE/CARBON MONOXIDE DETECTOR(S)          
2.8.C MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area rugs or areas obstructed from view. Please be aware that the inspector has your best interest in mind. It is recommended that qualified contractors be used in your further repair issues as it relates to the comments in this inspection report.

2(D) .  Master Bedroom

The inspector shall observe: Walls, ceiling, and floors; steps, stairways, balconies, and railings; and a representative number of doors and windows. The inspector shall: Operate a representative number of windows and interior doors; and report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; carpeting; or draperies, blinds, or other window treatments. As a general rule, cosmetic deficiencies are considered normal wear and tear and not reported. Determining the condition of insulated glass windows is not always possible due to temperature, weather and lighting conditions. It is advisable to check with the owner(s) for any additional information.
Styles & Materials
CEILING MATERIAL:
DRYWALL
WALL MATERIAL:
DRYWALL
FLOOR COVERING(S):
CARPET
DOOR(S):
RAISED PANEL
FRENCH DOORS
and
WINDOW TYPES:
DUAL PANE INSULATED
 
    IN NI R/R S M/I NP
2.0.D CEILINGS          
2.1.D WALLS          
2.2.D FLOORS          
2.3.D DOORS (Representative Number)          
2.4.D WINDOWS (Representative Number)          
2.5.D ELECTRICAL / OUTLETS / SWITCHES          
2.6.D CLOSET(S)          
2.7.D SMOKE/CARBON MONOXIDE DETECTOR(S)          
2.8.D MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

Comments:

2.1.D   Settlement cracking at the drywall
The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area rugs or areas obstructed from view. Please be aware that the inspector has your best interest in mind. It is recommended that qualified contractors be used in your further repair issues as it relates to the comments in this inspection report.

2(E) .  Hallway/Other

The inspector shall observe: Walls, ceiling, and floors; steps, stairways, balconies, and railings; and a representative number of doors and windows. The inspector shall: Operate a representative number of windows and interior doors; and report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; carpeting; or draperies, blinds, or other window treatments. As a general rule, cosmetic deficiencies are considered normal wear and tear and not reported. Determining the condition of insulated glass windows is not always possible due to temperature, weather and lighting conditions. It is advisable to check with the owner(s) for any additional information.
Styles & Materials
CEILING MATERIAL:
DRYWALL
WALL MATERIAL:
DRYWALL
FLOOR COVERING(S):
CERAMIC
DOOR(S):
FRENCH DOORS
WINDOW TYPES:
DUAL PANE INSULATED
 
    IN NI R/R S M/I NP
2.0.E CEILINGS          
2.1.E WALLS          
2.2.E FLOORS          
2.3.E DOORS (Representative Number)          
2.4.E WINDOWS (Representative Number)          
2.5.E ELECTRICAL / OUTLETS / SWITCHES          
2.6.E CLOSET(S)          
2.7.E SMOKE/CARBON MONOXIDE DETECTOR(S)        
2.8.E MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

Comments:

2.7.E  As of May 2010, A Carbon Monoxide device is now mandatory by state law (SB 183) for human occupied dwellings and must be a certified device by the State Fire Marshall, preferred locations are outside of all sleeping areas and hallways at all levels of structure. Combined Smoke /Carbon Monoxide detectors are acceptable, providing the carbon monoxide detector emits an audible sound different than the smoke detector. Battery powered , Plug In, or Hard Wired (with a battery back-up) detectors are acceptable.Battery life must be a minimum of a 5 year life span. The lack of such a device is a Safety Issue. Location should not be any higher than 5' from floor level.
The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area rugs or areas obstructed from view. Please be aware that the inspector has your best interest in mind. It is recommended that qualified contractors be used in your further repair issues as it relates to the comments in this inspection report.

2(F) .  Bonus Room

The inspector shall observe: Walls, ceiling, and floors; steps, stairways, balconies, and railings; and a representative number of doors and windows. The inspector shall: Operate a representative number of windows and interior doors; and report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; carpeting; or draperies, blinds, or other window treatments. As a general rule, cosmetic deficiencies are considered normal wear and tear and not reported. Determining the condition of insulated glass windows is not always possible due to temperature, weather and lighting conditions. It is advisable to check with the owner(s) for any additional information.
Styles & Materials
CEILING MATERIAL:
DRYWALL
WALL MATERIAL:
DRYWALL
FLOOR COVERING(S):
CERAMIC
DOOR(S):
FRENCH DOORS
WINDOW TYPES:
DUAL PANE INSULATED
 
    IN NI R/R S M/I NP
2.0.F CEILINGS          
2.1.F WALLS          
2.2.F FLOORS          
2.3.F DOORS (Representative Number)          
2.4.F WINDOWS (Representative Number)          
2.5.F ELECTRICAL / OUTLETS / SWITCHES          
2.6.F CLOSET(S)          
2.7.F MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area rugs or areas obstructed from view. Please be aware that the inspector has your best interest in mind. It is recommended that qualified contractors be used in your further repair issues as it relates to the comments in this inspection report.

2(G) .  Casitas

The inspector shall observe: Walls, ceiling, and floors; steps, stairways, balconies, and railings; and a representative number of doors and windows. The inspector shall: Operate a representative number of windows and interior doors; and report signs of abnormal or harmful water penetration into the building or signs of abnormal or harmful condensation on building components. The inspector is not required to observe: Paint, wallpaper, and other finish treatments on the interior walls, ceilings, and floors; carpeting; or draperies, blinds, or other window treatments. As a general rule, cosmetic deficiencies are considered normal wear and tear and not reported. Determining the condition of insulated glass windows is not always possible due to temperature, weather and lighting conditions. It is advisable to check with the owner(s) for any additional information.
Styles & Materials
CEILING MATERIAL:
DRYWALL
WALL MATERIAL:
DRYWALL
FLOOR COVERING(S):
CARPET
DOOR(S):
FRENCH DOORS
WINDOW TYPES:
DUAL PANE INSULATED
 
    IN NI R/R S M/I NP
2.0.G CEILINGS          
2.1.G WALLS          
2.2.G FLOORS          
2.3.G DOORS (Representative Number)          
2.4.G WINDOWS (Representative Number)          
2.5.G ELECTRICAL / OUTLETS / SWITCHES          
2.6.G CLOSET(S)          
2.7.G SMOKE/CARBON MONOXIDE DETECTOR(S)        
2.8.G MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

Comments:

2.3.G   Missing door stops, wall damage may occur.
2.7.G  Carbon Monoxide detector is required.
The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area rugs or areas obstructed from view. Please be aware that the inspector has your best interest in mind. It is recommended that qualified contractors be used in your further repair issues as it relates to the comments in this inspection report.

3(A) .  Master Bath

1st and 2nd story shower pans are visually inspected for leaks, but leaks often do not show except when the shower is in actual use. Determining if shower pans, tubs/shower surrounds are water tight is beyond the scope of this inspection. It is very important to maintain all grouting and caulking at the bath area(s). Water supply valves under sink vanities are not turned during this inspection. In doing so, it may subject the valve to leakage.

Styles & Materials
CEILING MATERIALS:
DRYWALL
WALL MATERIAL:
DRYWALL
FLOOR COVERING(S):
TILE
    IN NI R/R S M/I NP
3.0.A SINK(S) (Including Plumbing)          
3.1.A SINK BASE/CABINETRY/COUNTER TOP          
3.2.A ELECTRICAL (Outlets/ Wall Switches/Fixtures)          
3.3.A TOILET(S)(including plumbing)          
3.4.A SHOWER(S)(including plumbing)          
3.5.A TUB(S)(including plumbing)          
3.6.A SHOWER/TUB ENCLOSURE(S)          
3.7.A CEILINGS          
3.8.A WALLS          
3.9.A FLOORS          
3.10.A DOORS (Representative Number)          
3.11.A WINDOWS (Representative Number)          
3.12.A EXHAUST FAN(S)          
3.13.A MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

Comments:

3.0.A (1)  Plumbing leak under the sink, Right sink
3.0.A (2)  Loose/broken Hot water handle, Left sink
3.0.A (3)   Sink stopper is inoperable, Left sink
3.5.A   Tub drains slow
3.8.A   Settlement cracking, wall of the toilet area

In homes built to comply with the National Building Code (The Code), GFCI protection is required for most outdoor receptacles, since 1973, bathroom receptacles, since 1975, garage wall outlets, since 1978, kitchen receptacles, since 1987, and all receptacles in crawl spaces and unfinished basements, since 1990. Owners of homes that do not have GFCIs installed in all critical areas specified in the latest version of the Code, should consider having them installed.

3(B) .  Private Bath, Hall Bedroom

1st and 2nd story shower pans are visually inspected for leaks, but leaks often do not show except when the shower is in actual use. Determining if shower pans, tubs/shower surrounds are water tight is beyond the scope of this inspection. It is very important to maintain all grouting and caulking at the bath area(s). Water supply valves under sink vanities are not turned during this inspection. In doing so, it may subject the valve to leakage.

Styles & Materials
CEILING MATERIALS:
DRYWALL
WALL MATERIAL:
DRYWALL
FLOOR COVERING(S):
TILE
    IN NI R/R S M/I NP
3.0.B SINK(S) (Including Plumbing)          
3.1.B SINK BASE/CABINETRY/COUNTER TOP          
3.2.B ELECTRICAL (Outlets/ Wall Switches/Fixtures)          
3.3.B TOILET(S)(including plumbing)          
3.4.B SHOWER(S)(including plumbing)          
3.5.B TUB(S)(including plumbing)          
3.6.B SHOWER/TUB ENCLOSURE(S)          
3.7.B CEILINGS          
3.8.B WALLS          
3.9.B FLOORS          
3.10.B DOORS (Representative Number)          
3.11.B WINDOWS (Representative Number)          
3.12.B EXHAUST FAN(S)          
3.13.B MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

Comments:

3.0.B   Sink drains slow and stopper is inoperable. Possible clogged drain
3.3.B  Corrosion at the angle stop valve, recommend replacement.

In homes built to comply with the National Building Code (The Code), GFCI protection is required for most outdoor receptacles, since 1973, bathroom receptacles, since 1975, garage wall outlets, since 1978, kitchen receptacles, since 1987, and all receptacles in crawl spaces and unfinished basements, since 1990. Owners of homes that do not have GFCIs installed in all critical areas specified in the latest version of the Code, should consider having them installed.

3(C) .  Powder Room Bath

1st and 2nd story shower pans are visually inspected for leaks, but leaks often do not show except when the shower is in actual use. Determining if shower pans, tubs/shower surrounds are water tight is beyond the scope of this inspection. It is very important to maintain all grouting and caulking at the bath area(s). Water supply valves under sink vanities are not turned during this inspection. In doing so, it may subject the valve to leakage.

Styles & Materials
CEILING MATERIALS:
DRYWALL
WALL MATERIAL:
DRYWALL
FLOOR COVERING(S):
CERAMIC
    IN NI R/R S M/I NP
3.0.C SINK(S) (Including Plumbing)          
3.1.C SINK BASE/CABINETRY/COUNTER TOP          
3.2.C ELECTRICAL (Outlets/ Wall Switches/Fixtures)          
3.3.C TOILET(S)(including plumbing)          
3.4.C SHOWER(S)(including plumbing)          
3.5.C TUB(S)(including plumbing)          
3.6.C SHOWER/TUB ENCLOSURE(S)          
3.7.C CEILINGS          
3.8.C WALLS          
3.9.C FLOORS          
3.10.C DOORS (Representative Number)          
3.11.C WINDOWS (Representative Number)          
3.12.C EXHAUST FAN(S)          
3.13.C MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

In homes built to comply with the National Building Code (The Code), GFCI protection is required for most outdoor receptacles, since 1973, bathroom receptacles, since 1975, garage wall outlets, since 1978, kitchen receptacles, since 1987, and all receptacles in crawl spaces and unfinished basements, since 1990. Owners of homes that do not have GFCIs installed in all critical areas specified in the latest version of the Code, should consider having them installed.

3(D) .  Casitas Bath

1st and 2nd story shower pans are visually inspected for leaks, but leaks often do not show except when the shower is in actual use. Determining if shower pans, tubs/shower surrounds are water tight is beyond the scope of this inspection. It is very important to maintain all grouting and caulking at the bath area(s). Water supply valves under sink vanities are not turned during this inspection. In doing so, it may subject the valve to leakage.

Styles & Materials
CEILING MATERIALS:
DRYWALL
FLOOR COVERING(S):
TILE
 
    IN NI R/R S M/I NP
3.0.D SINK(S) (Including Plumbing)          
3.1.D SINK BASE/CABINETRY/COUNTER TOP          
3.2.D ELECTRICAL (Outlets/ Wall Switches/Fixtures)          
3.3.D TOILET(S)(including plumbing)          
3.4.D SHOWER(S)(including plumbing)          
3.5.D TUB(S)(including plumbing)          
3.6.D SHOWER/TUB ENCLOSURE(S)          
3.7.D CEILINGS          
3.8.D WALLS          
3.9.D FLOORS          
3.10.D DOORS (Representative Number)          
3.11.D WINDOWS (Representative Number)          
3.12.D EXHAUST FAN(S)          
3.13.D MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

Comments:

3.5.D   Missing tub drain stopper

In homes built to comply with the National Building Code (The Code), GFCI protection is required for most outdoor receptacles, since 1973, bathroom receptacles, since 1975, garage wall outlets, since 1978, kitchen receptacles, since 1987, and all receptacles in crawl spaces and unfinished basements, since 1990. Owners of homes that do not have GFCIs installed in all critical areas specified in the latest version of the Code, should consider having them installed.

4.  Laundry Area

A visual inspection only is performed at the laundry area(s). Appliances are not moved, operated or inspected. Plumbing is visually inspected, gas lines and 220 Volt outlets are not tested. The condition of the floors or walls behind appliances cannot be determined. Drain lines and water supply valves serving the plumbing are not operated. Water supply valves may be subject to leakage if turned.

Styles & Materials
LOCATION:
SEPERATE LAUNDRY ROOM
GAS SERVICE AVAILABLE:
YES
220 VOLT SERVICE AVAILABLE:
NO
DRYER POWER SOURCE:
NATURAL GAS
   
    IN NI R/R S M/I NP
4.0 LOCATION          
4.1 PLUMBING          
4.2 ELECTRICAL        
4.3 GAS SERVICE          
4.4 DRYER VENTING          
4.5 CABINETS / COUNTER TOPS          
4.6 CEILING          
4.7 WALLS          
4.8 FLOORING          
4.9 DOOR(S)          
4.10 EXHAUST FAN          
4.11 MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

Comments:

4.2   No Ground Fault Circuit Interrupters near the Washing machine or Service sink (Where Applicable). Recommend GFCI (ground fault circuit interrupter) outlets within 6 feet of a water source. Safety issue.
4.9  Missing the door stop, wall damage may occur.

In homes built to comply with the National Building Code (The Code), GFCI protection is required for most outdoor receptacles, since 1973, bathroom receptacles, since 1975, garage wall outlets, since 1978, kitchen receptacles, since 1987, and all receptacles in crawl spaces and unfinished basements, since 1990. Owners of homes that do not have GFCIs installed in all critical areas specified in the latest version of the Code, should consider having them installed.

5.  Garage

The inspection of the garage is of the visible and accessible area(s) only. The Inspector does not move stored or personal items. Determining heat resistance of firewalls is beyond the scope of this inspection, and therefor excluded.
Styles & Materials
GARAGE DOOR TYPE:
THREE CAR AUTOMATIC
ATTACHED
GARAGE DOOR MATERIAL:
ROLL UP
OPENER MANUFACTURER:
ANAHEIM DOOR
GARAGE FLOOR MATERIAL:
CONCRETE
PAINTED
   
    IN NI R/R S M/I NP
5.0 GARAGE DOOR OPERATORS          
5.1 CONDITION OF GARAGE DOOR(S)          
5.2 PEDESTRIAN DOOR(S)          
5.3 ELECTRICAL          
5.4 CEILINGS (including firewall protection)          
5.5 WALLS (including firewall protection)          
5.6 FLOORS          
5.7 WINDOWS (Representative Number)          
5.8 MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

Comments:

5.8  The structure is constructed with a residential fire sprinkler system, which is outside the scope of a home inspection. It is recommended to have the system tested/inspected upon move in and yearly beyond then 

In homes built to comply with the National Building Code (The Code), GFCI protection is required for most outdoor receptacles, since 1973, bathroom receptacles, since 1975, garage wall outlets, since 1978, kitchen receptacles, since 1987, and all receptacles in crawl spaces and unfinished basements, since 1990. Owners of homes that do not have GFCIs installed in all critical areas specified in the latest version of the Code, should consider having them installed.

6.  Attic and Roof Framing

The attic is inspected from the visible and accessible area(s) only. The Inspector does not move attic insulation for the inspection. The inspector does not inspect for or determine the "R" factor of the insulation. It is recommended for energy efficiency to have your local heating/cooling utility provider inspect the attic insulation.  

Styles & Materials
ATTIC INFO:
SCUTTLE HOLE
METHOD USED TO OBSERVE ATTIC:
FROM ENTRY
ROOF STRUCTURE:
MANUFACTURED TRUSS
SHEATHING TYPE:
OSB BOARD
ATTIC INSULATION:
FIBERGLASS
R-FACTOR IS UNKNOWN
VENTILATION:
ADEQUATE
    IN NI R/R S M/I NP
6.0 ATTIC ACCESS          
6.1 ATTIC INSULATION (Coverage)          
6.2 VENTILATION OF ATTIC          
6.3 ROOF STRUCTURE AND ATTIC FRAMING          
6.4 VISIBLE ELECTRICAL WIRING          
6.5 MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

7.  Exterior Components

The inspector shall observe: Wall cladding, flashings, and trim; entryway doors and a representative number of windows; decks, balconies, stoops, steps, areaways, porches and applicable railings; eaves, soffits, and fascias; and vegetation, grading, drainage, driveways, patios, walkways, and retaining walls with respect to their effect on the condition of the building. The inspector shall: Describe wall cladding materials; operate various entryway doors and a representative number of windows; The  inspector is not required to observe: Storm windows, storm doors, screening, shutters, awnings, and similar seasonal accessories; fences; presence of safety glazing in doors and windows; geological conditions; soil conditions; recreational facilities (including spas, saunas, steam baths, swimming pools, tennis courts, playground equipment, and other exercise, entertainment, or athletic facilities); detached buildings or structures; or presence or condition of buried fuel storage tanks. The inspector is not required to: Move personal items, panels, furniture, equipment, plant life, soil, or debris that obstructs access or visibility. Area(s) hidden from view by finished walls or stored items can not be inspected, so therefor are not part of this inspection. Minor cracks are typical in many foundations and most do not represent a structural problem. If major cracks are present, we routinely recommend a further evaluation be made by a qualified structural engineer. This inspection is not intended to address or include any geological conditions or site stability information. For information to address these concerns, if present, a geologist or soils engineer should be consulted. The inspection is visible in nature and does not attempt to determine drainage performance of the site or the condition of any under ground piping.
Styles & Materials
SIDING MATERIAL:
STUCCO
STONE VENEER
and
EXTERIOR ENTRY DOORS:
SERVICABLE
WALKWAY(S):
CONCRETE
DRIVEWAY:
CONCRETE
FENCING/GATES:
BLOCK WALLS
WROUGHT IRON
and
 
    IN NI R/R S M/I NP
7.0 EAVES, SOFFITS AND FASCIAS          
7.1 EXTERIOR WALL COVERING, FLASHING AND TRIM          
7.2 WINDOWS (Exterior)          
7.3 DOORS (Exterior)          
7.4 ELECTRICAL (Outlet(s) / Switches / Fixtures)          
7.5 DECKS, BALCONIES, STEPS, PORCHES, PATIO COVER(S) AND APPLICABLE RAILINGS          
7.6 DRIVEWAY, WALKWAY(S), PATIO SLAB(S), STOOP(S)          
7.7 FENCING / GATE(S)          
7.8 LANDSCAPING, GRADING, DRAINAGE (Excluding Irrigation System)          
7.9 MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

Comments:

7.1 (1)   Settlement cracking at the exterior stucco, recommend to seal areas to prevent moisture intrusion
7.1 (2)   Exterior grade level is too high. Recommend to adjust the height of the exterior grade level to 3"-4" below stucco weep screed and/or foundation footing and close sprinkler heads.
7.5  Peeling paint at the railings, recommend to prep and paint
7.6  Lifting walkway slabs
7.8 (1)  Front fountain is inoperable
7.8 (2)   Missing drain cap
The exterior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. It is recommended that qualified contractors be used in your further repair issues as it relates to the comments in this inspection report.

In homes built to comply with the National Building Code (The Code), GFCI protection is required for most outdoor receptacles, since 1973, bathroom receptacles, since 1975, garage wall outlets, since 1978, kitchen receptacles, since 1987, and all receptacles in crawl spaces and unfinished basements, since 1990. Owners of homes that do not have GFCIs installed in all critical areas specified in the latest version of the Code, should consider having them installed.

8.  Plumbing System

The inspector shall observe: Interior water supply and distribution system, including: piping materials, supports, and insulation; fixtures and faucets; functional flow; leaks; and cross connections; interior drain, waste, and vent system, including: traps; drain, waste, and vent piping; piping supports and pipe insulation; leaks; and functional drainage; hot water systems including: water heating equipment; normal operating controls; automatic safety controls; and chimneys, flues, and vents; fuel storage and distribution systems including: interior fuel storage equipment, supply piping, venting, and supports; leaks;  The inspector shall describe: water supply and distribution piping materials; drain, waste, and vent piping materials; water heating equipment; and location of main water supply shutoff device. The inspector shall operate various plumbing fixtures, including their faucets and various exterior faucets attached to the house, except where the flow end of the faucet is connected to an appliance. The inspector is not required to: State the effectiveness of anti-siphon devices; determine whether water supply and waste disposal systems are public or private; operate automatic safety controls; operate any valve except water closet flush valves, fixture faucets, and hose faucets; Observe: Water conditioning systems; fire and lawn sprinkler systems; on-site water supply quantity and quality; on-site waste disposal systems; foundation irrigation systems; spas, except as to functional flow and functional drainage; swimming pools; solar water heating equipment; or observe the system for proper sizing, design, or use of proper materials. Leakage or corrosion of underground piping can not be determined from this inspection, so therefor is excluded. Drain lines and water supply valves serving the plumbing are not operated. Water supply valves may be subject to leakage if turned.
Styles & Materials
UTILITY SERVICE:
WATER IS ON
PLUMBING SUPPLY:
COPPER
PLUMBING DISTRIBUTION:
COPPER
PLUMBING WASTE:
ABS
VISIBILITY IS LIMITED
LOCATION OF WATER HEATER:
GARAGE
CAPACITY:
50 GALLONS
MANUFACTURER:
RHEEM
YEAR OF MANUFACTURE:
2010
WATER HEATER POWER SOURCE:
NATURAL GAS
    IN NI R/R S M/I NP
8.0 HOT WATER HEATER(S), CONTROLS, FLUES AND VENTS          
8.1 HOT WATER HEATER SEISMIC STRAPPING          
8.2 GAS SUPPLY (Where Applicable)          
8.3 VISIBLE PLUMBING LINES          
8.4 HOSE FAUCET CONNECTION(S)          
8.5 WATER PRESSURE AT HOSE CONNECTION          
8.6 MAIN WATER SHUT-OFF (Location / Condition)          
8.7 MISCELLANEOUS        
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

Comments:

8.2  Although it may not have been plumbing code when the hot water heater was installed, a gas line sediment trap on the gas line prior to the appliance is recommended. This is recommended to protect the water heater system and prolong the life span of the component. A gas line sediment trap shall be provided on the gas line downstream of the shut off valve and as close to the inlet of the equipment as practical. CA PLUMBING CODE 1212.8. Recommend repairs by a licensed tradesman.
8.5   Water pressure is low. Optimum pressure is between 60-80 P.S.I. Recommend to contact the water municipal for a further inspection
8.6  The main shut off is the yellow lever located in garage. This is for your information. These controls are not turned or operated as to not to disturb the natural seating.
8.7 (1)   Recommend a catch/drain pan with a drain under the hot water heater
8.7 (2)  Water softener system was not inspected. Interested parties may want to inquire with the supplier of the equipment.
8.7 (3)  Drain line for the water softener has been pierced thru the stucco
The plumbing in the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Washing machine drain line for example cannot be checked for leaks or the ability to handle the volume during drain cycle. Older homes with galvanized supply lines or cast iron drain lines can be obstructed and barely working during an inspection but then fails under heavy use. If the water is turned off or not used for periods of time (like a vacant home waiting for closing) rust or deposits within the pipes can further clog the piping system. Please be aware that the inspector has your best interest in mind. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

9.  Heating

The inspector shall observe permanently installed heating systems including: Heating equipment; normal operating controls; automatic safety controls; chimneys, flues, and vents, where readily visible; solid fuel heating devices; heat distribution systems including fans, pumps, ducts and piping, with supports, insulation, air filters, registers, radiators, fan coil units, connectors; and the presence of an installed heat source in each room. The inspector shall describe: Energy source; and heating equipment and distribution type. The inspector shall operate the systems using normal operating controls. The inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance. The inspector IS NOT required to: Operate heating systems when weather conditions or other circumstances may cause equipment damage; operate automatic safety controls; ignite or extinguish pilot lights; or Observe: The interior of flues; fireplace insert flue connections; humidifiers; electronic air filters; or the uniformity or adequacy of heat supply to the various rooms. The inspector is not equiped to inspect furnace heat exchangers for evidence of cracks or holes, as this can only be done by dismantling the unit, which must be performed by a qualified tradesperson. This is beyond the scope of our inspection. Gas supply lines are not normally fully visible. Under ground gas lines and/or leaks are excluded from this inspection.

 NOTE: Asbestos materials have been commonly used in heating systems. Determining the presence of asbestos can ONLY be determined by laboratory testing and is beyond the scope of this inspection.

Styles & Materials
GAS SUPPLY:
ON
LOCATION OF PRIMARY UNIT:
ATTIC
CEILING UNIT
and
HEAT TYPE:
FORCED AIR UNIT (FAU)
HEAT PUMP (FORCED AIR)
and
ENERGY SOURCE:
NATURAL GAS
WATER/ELECTRIC
and
NUMBER OF HEAT SYSTEMS:
TWO
MANUFACTURER:
CARRIER
FIRST CO.
and
YEAR OF MANUFACTURE:
SAME AS DWELLING
FILTER TYPE:
DISPOSABLE
DUCTWORK:
FLEXIBLE ROUND
And
INSULATED
TYPES OF FIREPLACES:
GAS
   
    IN NI R/R S M/I NP
9.0 HEATING EQUIPMENT          
9.1 LOCATION OF PRIMARY UNIT          
9.2 GAS SUPPLY (Where Applicable)          
9.3 NORMAL OPERATING CONTROLS          
9.4 FILTRATION          
9.5 FLUES AND VENTS (For Furnace)          
9.6 DUCT AIR SUPPLY          
9.7 AIR PLENUM          
9.8 FIREPLACE(S)          
9.9 GAS METER          
9.10 MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

Comments:

9.0   No response from the Casitas furnace unit when tested. Recommend a further inspection by a HVAC Contractor
9.4  Improper size filter
9.8 (1)   Gas line should be of a flexible Rigid material to prevent breakage in case of an earthquake.
9.8 (2)  Broken handle at the fireplace screen, Family Room
The heating system of this home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat contractor would discover. Please be aware that the inspector has your best interest in mind. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

10.  Central Air Conditioning

The inspector shall observe: Central air conditioning and permanently installed cooling systems including: Cooling and air handling equipment; and normal operating controls. Distribution systems including: Fans, pumps, ducts and piping, with associated supports, dampers, insulation, air filters, registers, fan-coil units; and the presence of an installed cooling source in each room. The inspector shall describe: Energy sources; and cooling equipment type. The inspector shall operate the systems using normal operating controls. The inspector shall open readily openable access panels provided by the manufacturer or installer for routine homeowner maintenance The inspector is not required to: Observe window air conditioners or operate cooling systems when weather conditions or other circumstances may cause equipment damage; observe non-central air conditioners; or observe the uniformity or adequacy of cool-air supply to the various rooms.
Styles & Materials
MANUFACTURER:
CARRIER
YEAR OF MANUFACTURE:
APPEARS SAME AS DWELLING
COOLING EQUIPMENT TYPE:
CENTRAL AIR CONDITION UNIT
NUMBER OF A/C UNITS:
TWO
   
    IN NI R/R S M/I NP
10.0 COOLING AND AIR HANDLER EQUIPMENT          
10.1 NORMAL OPERATING CONTROLS          
10.2 RETURN AIR TEMPERATURE DROP          
10.3 CONDENSATION LINE          
10.4 ELECTRICAL          
10.5 PROPER AIR CIRCULATION CLEARANCE AT CONDENSER          
10.6 MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

The cooling system of this home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed HVAC contractor would discover (Heating, Ventilation, and Air Conditioning). Please be aware that the inspector has your best interest in mind.  It is recommended that qualified contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.

11.  Electrical System

The inspector shall observe: Service entrance conductors; service equipment, grounding equipment, main over current device, and main and distribution panels; amperage and voltage ratings of the service; branch circuit conductors, their over current devices, and the compatibility of their ampacities and voltages; the operation of a representative number of installed ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls; The polarity and grounding of various receptacles within six feet of interior plumbing fixtures, and various receptacles in the garage or carport, and on the exterior of inspected structures; The operation of ground fault circuit interrupters; and smoke detectors. The inspector shall describe: Service amperage and voltage; service entry conductor materials; service type as being overhead or underground; and location of main and distribution panels. The inspector shall report any observed aluminum branch circuit wiring. The inspector shall report on presence or absence of smoke detectors, and operate their test function, if accessible, except when detectors are part of a central system. The inspector is not required to: Insert any tool, probe, or testing device inside the panels; test or operate any over current device except ground fault circuit interrupters; dismantle any electrical device or control other than to remove the covers of the main and auxiliary distribution panels; or Observe: Low voltage systems; including landscape lighting, security system devices, heat detectors, or carbon monoxide detectors; telephone, security, cable TV, intercoms, or other ancillary wiring that is not a part of the primary electrical distribution system; or built-in vacuum equipment.

Any electrical repairs attempted by anyone other than a licensed electrician should be approached with caution.

Aluminum wiring requires periodic inspection and maintenance by a qualified electrician due to the heating and cooling effects.

Styles & Materials
UTILTY STATUS:
ELECTRIC IS ON
PANEL TYPE:
CIRCUIT BREAKERS
PANEL CAPACITY:
200 AMP
SERVICE ENTRANCE CONDUCTORS:
BELOW GROUND
BRANCH WIRE:
COPPER
MANUFACTURE:
SQUARE D
LOCATION OF SERVICE PANEL:
LEFT SIDE, FACING STRUCTURE
   
    IN NI R/R S M/I NP
11.0 LOCATION OF SERVICE PANEL(S)          
11.1 CIRCUIT BREAKERS OR FUSES INSIDE PANEL          
11.2 VISIBLE WIRING AT SERVICE PANEL          
11.3 CLEARANCE AROUND SERVICE PANEL          
11.4 SERVICE ENTRANCE CONDUCTORS          
11.5 SERVICE AND GROUNDING EQUIPMENT          
11.6 MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

The electrical system of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Outlets were not removed and the inspection was only visual. Any outlet not accessible (behind the refrigerator for example) was not inspected or accessible. Please be aware that the inspector has your best interest in mind. It is recommended that qualified contractors be used in your further or repair issues as it relates to the comments in this inspection report.

In homes built to comply with the National Building Code (The Code), GFCI protection is required for most outdoor receptacles, since 1973, bathroom receptacles, since 1975, garage wall outlets, since 1978, kitchen receptacles, since 1987, and all receptacles in crawl spaces and unfinished basements, since 1990. Owners of homes that do not have GFCIs installed in all critical areas specified in the latest version of the Code, should consider having them installed.

12.  Roof System, Drainage, Roof Penetrations

The inspector shall observe: Roof covering; Roof drainage systems; Flashings; Skylights, chimneys, and roof penetrations; and signs of' leaks or abnormal condensation on building components. The inspector shall: Describe the type of roof covering materials; and report the methods used to observe the roofing. The inspector is not required to: Walk on the roofing; or observe attached accessories including but not limited to solar systems, antennae, and lightning arrestors. The foregoing is an opinion of the general condition and quality of the roof covering. The inspector cannot and does not render opinions or warranty as to whether the roof leaks or may be subject to leaks in the future. This report is issued in consideration of this disclaimer. The only way to determine the water tightness is to observe the roof during a prolonged rain fall. Any additional concerns should be addressed to a licensed roofing contractor and request a roof certification and /or warranty. This visual inspection is not intended to be a full encompassing roof inspection, and NO warranty or implied guarantees are issued. No opinion on life expectancy or existing age is issued.
Styles & Materials
VIEWED ROOF COVERING FROM:
LADDER
GROUND
and
ROOF COVERING:
TILE
ROOF STYLE:
HIP & VALLEY
    IN NI R/R S M/I NP
12.0 ROOF COVERINGS        
12.1 EXPOSED FLASHINGS          
12.2 ROOF PENETRATIONS          
12.3 GUTTER SYSTEM          
12.4 CHIMNEY(S)          
12.5 MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

Comments:

12.0 (1)   Tree limbs that are in contact with roof or hanging near roof should be trimmed back a minimum of 3 feet from the roof.
12.0 (2)  The inspector did not walk upon the roof due to it's fragile nature. Roof covering was inspected from visible points, ground, windows, ladders, etc. Any further concerns from the client should be directed to a licensed roofer. Walking upon the roof by the inspector will have to be performed at the current owners' request and a signed waiver of liability against potential damage must be signed prior to for authorization.
The roof of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas of concern, some areas can go unnoticed. Roof coverings and skylights can appear to be leak proof during inspection and weather conditions. Our inspection makes an attempt to find a leak but sometimes cannot. Please be aware that the inspector has your best interest in mind. It is recommended that qualified contractors be used in your further repair issues as it relates to the comments in this inspection report.

13.  Swimming Pools and Equipment

A visual inspection only is performed of the swimming pool and/or spa. No water quality testing is performed. Heater equipment, pumps and filters are inspected for visible leakage, but not for quality of operation. We do not render opinions on the life expectancy of any equipment or material. No opinions are offered on the water tightness of any pool or spa plaster,gunite and/or pebble coating. It is common to have some seepage occur.

THIS IS AN OPERATIONAL INSPECTION OF THE ITEMS LISTED AND NOT A CERTIFICATION OF ANY SORT. THIS POOL/SPA REPORT IS A VISUAL INSPECTION AND OPERATIONAL TESTOF THE ABOVE GROUND EQUIPMENT ONLY.INSPECTION OF POOL/SPA SURFACE OR CONSEALED COMPONENTS ARE NOT WITHIN THE SCOPE OF THIS REPORT. CLIENT IS ADVISED TO CONSULT WITH AN APPROPRIATE SPECIALIST IF CONCERNED BY THE CONDITIONS IDENTIFIED IN THIS INSPECTION AND REPORT OR WHICH THEY MAY HAVE OBSERVED.

Styles & Materials
STYLE:
IN GROUND & HEATED
WALL MATERIALS:
PEBBLE COAT
WATER SYSTEM:
SALT WATER
HEATER:
PENTAIR
   
    IN NI R/R S M/I NP
13.0 SURFACE WALLS AND FLOOR OF POOL/SPA          
13.1 DECKING          
13.2 COPING          
13.3 PUMPS FOR CIRCULATION OF WATER          
13.4 OPERATIONAL CONDITION OF POOL/SPA          
13.5 FILTRATION/SKIMMER          
13.6 POOL/SPA HEATERS          
13.7 LIGHTING (Pool/Spa)          
13.8 ELECTRICAL          
13.9 SAFETY EQUIPMENT          
13.10 MISCELLANEOUS          
    IN NI R/R S M/I NP
IN= Inspected, NI= Not Inspected, R/R= Repair or Replace, S= Safety, M/I= Maintenance/Information, NP= Not Present

Comments:

13.2  Seepage at the spa coping
13.4 (1)  Pool Pilot Salt maker Service light is flashing, recommend a further review by a pool technician
13.4 (2)  Water feature is inoperable possibly due to an inoperable GFCI outlet
13.4 (3)  Missing spa jets
13.7  Pool/spa lighting is inoperable
13.8  Inoperable GFCI outlet, no power
13.9  Right side wood gate does not automatically close which is required for child safety reasons
  INVOICE

1st Choice Property Inspections
20432 Alcalde
Ste D
Laguna Hills, Ca 92653
949.413.3650 Cell
888.202.4642 Office
email: youroneinspector@gmail.com
www.1stchoicepropertyinspections.net
Inspected By:  Gregg Traum
Inspection Date: 12/8/2015
Report ID: 15-6051

Customer Info: Inspection Property:
Jim Shoe


Customer's Real Estate Professional:
Joe Realtor
ABC Realty  
10 Portalon
Ladera Ranch Ca 92694
 

Inspection Fee:

ServicePriceAmountSub-Total
2,501 - 3,500 SQ. FT. 425.00 1 425.00
Swimming Pool/Spa 50.00 1 50.00

Tax $0.00
Total Price $475.00

Payment Method: Check
Payment Status: Paid At Time Of Inspection
Note: THANK YOU FOR YOUR BUSINESS!!