Date: 12/8/2015 | Time: 11:00 AM | Report ID: 15-6051 |
Property: 10 Portalon Ladera Ranch Ca 92694 |
Customer: Jim Shoe |
Real Estate Professional: Joe Realtor
|
Comment Key or Definitions
The following definitions of comment descriptions represent this inspection report. Any recommendations by the inspector to repair or replace suggests a further inspection by a qualified tradesperson.
In no way should this inspection and/or report be construed as a guarantee or warranty against structural / component / item defects or failure, presently or in the future. No expressed or implied guarantees/warranties are or were given.
Inspections are not performed to determine if additions and/or improvements are permitted. It is recommended that any concerns regarding building permits be directed to the owner and/or the city/county building department.
We certify that our inspector has no interest, present or contemplated, in this property or it's improvements and we have no involvement with tradespeople derived from any sales or improvements.
You may view and print your report by visiting the web site at: www.1stChoicePropertyInspections.net .
Comments highlighted in "RED" print requires attention due to defects, conditions or safety issues.
Digital photos may not be provided for every concern or defect. NOT ALL DEFECTS OR CONCERNS ARE PHOTOGRAPHED.
Inspected (IN) = Visually observed the item, component or unit and if no other comments were made then it appeared to be functioning as intended allowing for normal wear and tear.
Not Inspected (NI) = Did not inspect this item, component or unit and made no representations of whether or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP) = This item, component or unit is not present in this structure.
Repair or Replace (R/R) = The item, component or unit is not functioning as intended or needs further inspection by a qualified tradesperson. Items, components or units that can be repaired to satisfactory condition may not need replacement.
Safety Item (S) = The item, component and/or unit does not conform to today's modern safety standards. Item, component and/or unit may function as intended, however does not provide modern safety characteristics, or may be missing and/or malfunctioning: Recommend repair or improvement
Maintenance or Informational (M/I) = Comments and/or recommendations are for maintenance or informational purposes only.
It is highly recommended that the CLIENT attend the inspection so that they may be briefed on any findings so that there are no misinterpretations of this report. It is suggested that all interested parties thoroughly read the "General Summary" section of this report as well as it's entirety.
This inspection and report is intended solely for the client. Any reproduction or forwarding of this report to third parties without the express written consent of the client is prohibited.
Homes constructed prior to 1978 pose the possibility of Lead Paint. This is to be considered notice to client(s) and interested parties to this inspection report, that a Lead Paint inspection WAS NOT PERFORMED. If the client and/or interested parties to this inspection report are concerned with the possibility of Lead Paint contamination, we suggest a further evaluation by a tradesman qualified in that field. This notice shall hold 1st Choice Property Inspections, it's owner(s), officer(s) and vested partner(s), if any, harmless of any such Lead Paint conditions, or health issues if any exist.
Inspector: Gregg Traum | Style of Home: MULTI LEVEL SINGLE FAMILY | Occupancy Status: FURNISHED & OCCUPIED |
Estimated Age Of Home: Approximatly 5-8 years | Area: SUBURB | Viewed From: STREET |
Main Entrance Faces: WEST | Persons Present: BUYER, SELLER, SELLING AGENT | Weather: HOT & HUMID |
Approximate Temperature: Over 80 | Rain in last 3 days: NO |
![]() 1st Choice Property Inspections 20432 Alcalde |
Customer |
Property Address |
The following items or discoveries indicate that these systems and/or components do not function as intended or adversely effect the habitability of the dwelling; or appear to warrant further investigation by a specialist, or requires subsequent observation. This summary shall not contain recommendations for routine upkeep of a system or component to keep it in proper functioning condition, or recommendations to upgrade or enhance the function of the dwelling. This summary "Is Not" the entire report. The complete report may include additional information of concern to the client. It is recommended that the client read this report in it's entirety.
1.6 | RANGE VENT HOOD OPERATION |
Repair or Replace | |
Missing control knob ![]() 1.6 Item 1(Picture)
|
1.9 | CABINETS |
Repair or Replace | |
Damaged sink shelf. Recommend the appropriate tradesman to correct ![]() 1.9 Item 1(Picture)
|
2.5.A | ELECTRICAL / OUTLETS / SWITCHES |
Repair or Replace | |
Inoperable ceiling light, possible bulb ![]() 2.5.A Item 1(Picture)
|
2.1.D | WALLS |
Repair or Replace | |
Settlement cracking at the drywall ![]() 2.1.D Item 1(Picture)
|
2.7.E | SMOKE/CARBON MONOXIDE DETECTOR(S) |
Repair or Replace, Safety | |
As of May 2010, A Carbon Monoxide device is now mandatory by
state law (SB 183) for human occupied dwellings and must be a
certified device by the State Fire Marshall, preferred locations are
outside of all sleeping areas and hallways at all levels of structure.
Combined Smoke /Carbon Monoxide detectors are acceptable,
providing the carbon monoxide detector emits an audible sound
different than the smoke detector. Battery powered , Plug In, or Hard
Wired (with a battery back-up) detectors are acceptable.Battery life
must be a minimum of a 5 year life span. The lack of such a device
is a Safety Issue. Location should not be any higher than 5'
from floor level. |
2.3.G | DOORS (Representative Number) |
Repair or Replace | |
Missing door stops, wall damage may occur. |
2.7.G | SMOKE/CARBON MONOXIDE DETECTOR(S) |
Repair or Replace, Safety | |
Carbon Monoxide detector is required. |
3.0.A | SINK(S) (Including Plumbing) |
Repair or Replace | |
(1) Plumbing leak under the sink, Right sink ![]() 3.0.A Item 1(Picture)
|
|
(2) Loose/broken Hot water handle, Left sink ![]() 3.0.A Item 2(Picture)
|
|
(3)
Sink stopper is inoperable, Left sink ![]() 3.0.A Item 3(Picture)
|
3.5.A | TUB(S)(including plumbing) |
Repair or Replace | |
Tub drains slow |
3.8.A | WALLS |
Repair or Replace | |
Settlement cracking, wall of the toilet area ![]() 3.8.A Item 1(Picture)
|
3.0.B | SINK(S) (Including Plumbing) |
Repair or Replace | |
Sink drains slow and stopper is inoperable. Possible clogged drain ![]() 3.0.B Item 1(Picture)
|
3.3.B | TOILET(S)(including plumbing) |
Repair or Replace | |
Corrosion at the angle stop valve, recommend replacement. ![]() 3.3.B Item 1(Picture)
|
3.5.D | TUB(S)(including plumbing) |
Repair or Replace | |
Missing tub drain stopper ![]() 3.5.D Item 1(Picture)
|
4.2 | ELECTRICAL |
Repair or Replace, Safety | |
No Ground Fault Circuit Interrupters near the Washing machine or Service sink (Where Applicable).
Recommend GFCI (ground fault circuit interrupter) outlets within 6 feet of a water source. Safety issue. ![]() 4.2 Item 1(Picture)
|
4.9 | DOOR(S) |
Repair or Replace | |
Missing the door stop, wall damage may occur. ![]() 4.9 Item 1(Picture)
|
5.8 | MISCELLANEOUS |
Not Inspected | |
The structure is constructed with a residential fire sprinkler system, which is outside the scope of a home
inspection. It is recommended to have the system tested/inspected upon move in and yearly beyond then ![]() 5.8 Item 1(Picture)
|
7.1 | EXTERIOR WALL COVERING, FLASHING AND TRIM |
Repair or Replace | |
(1)
Settlement cracking at the exterior stucco, recommend to seal areas to prevent moisture intrusion ![]() 7.1 Item 1(Picture)
![]() 7.1 Item 2(Picture)
|
|
(2)
Exterior grade level is too high. Recommend to adjust the height of the exterior grade level to 3"-4" below
stucco weep screed and/or foundation footing and close sprinkler heads. ![]() 7.1 Item 3(Picture)
![]() 7.1 Item 4(Picture)
|
7.5 | DECKS, BALCONIES, STEPS, PORCHES, PATIO COVER(S) AND APPLICABLE RAILINGS |
Repair or Replace | |
Peeling paint at the railings, recommend to prep and paint ![]() 7.5 Item 1(Picture)
![]() 7.5 Item 2(Picture)
|
7.6 | DRIVEWAY, WALKWAY(S), PATIO SLAB(S), STOOP(S) |
Repair or Replace | |
Lifting walkway slabs ![]() 7.6 Item 1(Picture)
|
7.8 | LANDSCAPING, GRADING, DRAINAGE (Excluding Irrigation System) |
Repair or Replace | |
(1) Front fountain is inoperable ![]() 7.8 Item 1(Picture)
|
|
(2)
Missing drain cap ![]() 7.8 Item 2(Picture)
|
8.2 | GAS SUPPLY (Where Applicable) |
Repair or Replace | |
Although it may not have been plumbing code when the hot water heater was installed, a gas line
sediment trap on the gas line prior to the appliance is recommended. This is recommended to protect
the water heater system and prolong the life span of the component. A gas line sediment trap shall be
provided on the gas line downstream of the shut off valve and as close to the inlet of the equipment as
practical. CA PLUMBING CODE 1212.8. Recommend repairs by a licensed tradesman. ![]() 8.2 Item 1(Picture)
![]() 8.2 Item 2(Picture)
|
8.5 | WATER PRESSURE AT HOSE CONNECTION |
Repair or Replace | |
Water pressure is low. Optimum pressure is between 60-80 P.S.I. Recommend to contact the water
municipal for a further inspection ![]() 8.5 Item 1(Picture)
|
8.6 | MAIN WATER SHUT-OFF (Location / Condition) |
Maintenance/Information | |
The main shut off is the yellow lever located in garage. This is for your information. These controls are not
turned or operated as to not to disturb the natural seating. ![]() 8.6 Item 1(Picture)
|
8.7 | MISCELLANEOUS |
Not Inspected, Repair or Replace | |
(1)
Recommend a catch/drain pan with a drain under the hot water heater ![]() 8.7 Item 1(Picture)
|
|
(2) Water softener system was not inspected. Interested parties may want to inquire with the supplier of the
equipment. ![]() 8.7 Item 2(Picture)
|
|
(3) Drain line for the water softener has been pierced thru the stucco ![]() 8.7 Item 3(Picture)
![]() 8.7 Item 4(Picture)
|
9.0 | HEATING EQUIPMENT |
Repair or Replace | |
No response from the Casitas furnace unit when tested. Recommend a further inspection by a HVAC
Contractor |
9.4 | FILTRATION |
Repair or Replace | |
Improper size filter ![]() 9.4 Item 1(Picture)
![]() 9.4 Item 2(Picture)
|
9.8 | FIREPLACE(S) |
Repair or Replace | |
(1)
Gas line should be of a flexible Rigid material to prevent breakage in case of an earthquake. ![]() 9.8 Item 1(Picture)
![]() 9.8 Item 2(Picture)
|
|
(2) Broken handle at the fireplace screen, Family Room ![]() 9.8 Item 3(Picture)
|
12.0 | ROOF COVERINGS |
Repair or Replace, Maintenance/Information | |
(1)
Tree limbs that are in contact with roof or hanging near roof should be trimmed back a minimum of 3 feet
from the roof. ![]() 12.0 Item 1(Picture)
![]() 12.0 Item 2(Picture)
|
|
(2) The inspector did not walk upon the roof due to it's fragile nature. Roof covering was inspected from visible
points, ground, windows, ladders, etc. Any further concerns from the client should be directed to a licensed
roofer. Walking upon the roof by the inspector will have to be performed at the current owners' request and
a signed waiver of liability against potential damage must be signed prior to for authorization. |
13.2 | COPING |
Repair or Replace | |
Seepage at the spa coping ![]() 13.2 Item 1(Picture)
|
13.4 | OPERATIONAL CONDITION OF POOL/SPA |
Repair or Replace | |
(1) Pool Pilot Salt maker Service light is flashing, recommend a further review by a pool technician ![]() 13.4 Item 1(Picture)
|
|
(2) Water feature is inoperable possibly due to an inoperable GFCI outlet ![]() 13.4 Item 2(Picture)
![]() 13.4 Item 3(Picture)
|
|
(3) Missing spa jets ![]() 13.4 Item 4(Picture)
|
13.7 | LIGHTING (Pool/Spa) |
Repair or Replace | |
Pool/spa lighting is inoperable ![]() 13.7 Item 1(Picture)
![]() 13.7 Item 2(Picture)
|
13.8 | ELECTRICAL |
Repair or Replace | |
Inoperable GFCI outlet, no power ![]() 13.8 Item 1(Picture)
|
13.9 | SAFETY EQUIPMENT |
Repair or Replace | |
Right side wood gate does not automatically close which is required for child safety reasons ![]() 13.9 Item 1(Picture)
|
Maytag Corp. issued a recall of 7.1 million dishwashers sold under the MAYTAG, AMANA, JENN-AIR, ADMIRAL, MAGIC CHEF, PERFORMA by Maytag, and CROSLEY brands after reports of fires starting due to electrical problems with the heating elements as reported by the U.S. Consumer Product Safety Commission in June 2010.
All the recalled dishwashers have plastic interiors and were sold nation wide between February 2006 thru April 2010 for between $250 & $900. They came in either black, bisque, white, silver or stainless front panels.
To determine if you have one of these recalled dishwashers, look for the model and serial numbers on the Left side of the door opening.
The recalled machines will have serial numbers starting with any of the following:
NW39, NW40, NW41, NW42, NW43, NW44, NW45, NW46, NW47, NW48, NW49, NW50, NW51, NY01, NY02, NY03, NY04, NY05, NY06, NY07, NY08, NY09, NY10, NY11, NY12, NY13, NY14, NY15, NY16, NY17, NY18, NY19 or Ending with any of the following: JC, JE, JG, JJ, JL, JN, JP, JR, JT, JV, JX, LA, LC, LE, LG, LJ, LL, LN, LP, LT, LV, LX, NA, NC, NE, NG, NJ, NL, NN, NP, NR.
If you have one of these dishwashers, you are urged to stop using it immediately and disconnect the power supply by either shutting off it's circuit breaker or by pulling out it's fuse.
Maytag will repair the recalled machines in-house or provide a rebate if a consumer decided to buy certain new models with stainless steel interiors. To schedule a repair or get a rebate, call MAYTAG @ 1-800-544-5513 or go to the company's recall site.
KITCHEN SINK: STAINLESS STEEL |
COUNTERTOP: GRANITE |
RANGE/COOK TOP: GAS WITH ELECTRIC IGNITION |
DISHWASHER: APPEARS SERVICABLE |
EXHAUST / RANGE HOOD: VENTED |
BUILT-IN MICROWAVE: APPEARS SERVICABLE |
FLOOR COVERING: CERAMIC |
IN | NI | R/R | S | M/I | NP | ||
1.0 | KITCHEN SINK (Type) | • | |||||
1.1 | PLUMBING (Including Fixtures) | • | |||||
1.2 | FOOD WASTE DISPOSER | • | |||||
1.3 | ELECTRICAL (Outlets / Wall Switches / Fixtures) | • | |||||
1.4 | DISHWASHER OPERATION | • | |||||
1.5 | RANGE(S) / COOKTOP(S) OPERATION | • | |||||
1.6 | RANGE VENT HOOD OPERATION | • | |||||
1.7 | MICROWAVE COOKING EQUIPMENT | • | |||||
1.8 | COUNTER TOPS | • | |||||
1.9 | CABINETS | • | |||||
1.10 | CEILINGS | • | |||||
1.11 | WALLS | • | |||||
1.12 | FLOORS | • | |||||
1.13 | WINDOWS (Representative Number) | • | |||||
1.14 | MISC. | • | |||||
IN | NI | R/R | S | M/I | NP |
CEILING MATERIAL: DRYWALL OPEN BEAM and |
WALL MATERIAL: DRYWALL |
FLOOR COVERING(S): CERAMIC |
DOOR(S): FRENCH DOORS |
WINDOW TYPES: DUAL PANE INSULATED |
IN | NI | R/R | S | M/I | NP | ||
2.0.A | CEILINGS | • | |||||
2.1.A | WALLS | • | |||||
2.2.A | FLOORS | • | |||||
2.3.A | DOORS (Representative Number) | • | |||||
2.4.A | WINDOWS (Representative Number) | • | |||||
2.5.A | ELECTRICAL / OUTLETS / SWITCHES | • | |||||
2.6.A | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
CEILING MATERIAL: DRYWALL |
WALL MATERIAL: DRYWALL |
FLOOR COVERING(S): CERAMIC |
DOOR(S): FRENCH DOORS |
WINDOW TYPES: DUAL PANE INSULATED |
IN | NI | R/R | S | M/I | NP | ||
2.0.B | CEILINGS | • | |||||
2.1.B | WALLS | • | |||||
2.2.B | FLOORS | • | |||||
2.3.B | DOORS (Representative Number) | • | |||||
2.4.B | WINDOWS (Representative Number) | • | |||||
2.5.B | ELECTRICAL / OUTLETS / SWITCHES | • | |||||
2.6.B | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
CEILING MATERIAL: DRYWALL |
WALL MATERIAL: DRYWALL |
FLOOR COVERING(S): CARPET |
DOOR(S): HOLLOW CORE RAISED PANEL |
WINDOW TYPES: DUAL PANE INSULATED |
IN | NI | R/R | S | M/I | NP | ||
2.0.C | CEILINGS | • | |||||
2.1.C | WALLS | • | |||||
2.2.C | FLOORS | • | |||||
2.3.C | DOORS (Representative Number) | • | |||||
2.4.C | WINDOWS (Representative Number) | • | |||||
2.5.C | ELECTRICAL / OUTLETS / SWITCHES | • | |||||
2.6.C | CLOSET(S) | • | |||||
2.7.C | SMOKE/CARBON MONOXIDE DETECTOR(S) | • | |||||
2.8.C | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
CEILING MATERIAL: DRYWALL |
WALL MATERIAL: DRYWALL |
FLOOR COVERING(S): CARPET |
DOOR(S): RAISED PANEL FRENCH DOORS and |
WINDOW TYPES: DUAL PANE INSULATED |
IN | NI | R/R | S | M/I | NP | ||
2.0.D | CEILINGS | • | |||||
2.1.D | WALLS | • | |||||
2.2.D | FLOORS | • | |||||
2.3.D | DOORS (Representative Number) | • | |||||
2.4.D | WINDOWS (Representative Number) | • | |||||
2.5.D | ELECTRICAL / OUTLETS / SWITCHES | • | |||||
2.6.D | CLOSET(S) | • | |||||
2.7.D | SMOKE/CARBON MONOXIDE DETECTOR(S) | • | |||||
2.8.D | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
CEILING MATERIAL: DRYWALL |
WALL MATERIAL: DRYWALL |
FLOOR COVERING(S): CERAMIC |
DOOR(S): FRENCH DOORS |
WINDOW TYPES: DUAL PANE INSULATED |
IN | NI | R/R | S | M/I | NP | ||
2.0.E | CEILINGS | • | |||||
2.1.E | WALLS | • | |||||
2.2.E | FLOORS | • | |||||
2.3.E | DOORS (Representative Number) | • | |||||
2.4.E | WINDOWS (Representative Number) | • | |||||
2.5.E | ELECTRICAL / OUTLETS / SWITCHES | • | |||||
2.6.E | CLOSET(S) | • | |||||
2.7.E | SMOKE/CARBON MONOXIDE DETECTOR(S) | • | • | ||||
2.8.E | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
CEILING MATERIAL: DRYWALL |
WALL MATERIAL: DRYWALL |
FLOOR COVERING(S): CERAMIC |
DOOR(S): FRENCH DOORS |
WINDOW TYPES: DUAL PANE INSULATED |
IN | NI | R/R | S | M/I | NP | ||
2.0.F | CEILINGS | • | |||||
2.1.F | WALLS | • | |||||
2.2.F | FLOORS | • | |||||
2.3.F | DOORS (Representative Number) | • | |||||
2.4.F | WINDOWS (Representative Number) | • | |||||
2.5.F | ELECTRICAL / OUTLETS / SWITCHES | • | |||||
2.6.F | CLOSET(S) | • | |||||
2.7.F | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
CEILING MATERIAL: DRYWALL |
WALL MATERIAL: DRYWALL |
FLOOR COVERING(S): CARPET |
DOOR(S): FRENCH DOORS |
WINDOW TYPES: DUAL PANE INSULATED |
IN | NI | R/R | S | M/I | NP | ||
2.0.G | CEILINGS | • | |||||
2.1.G | WALLS | • | |||||
2.2.G | FLOORS | • | |||||
2.3.G | DOORS (Representative Number) | • | |||||
2.4.G | WINDOWS (Representative Number) | • | |||||
2.5.G | ELECTRICAL / OUTLETS / SWITCHES | • | |||||
2.6.G | CLOSET(S) | • | |||||
2.7.G | SMOKE/CARBON MONOXIDE DETECTOR(S) | • | • | ||||
2.8.G | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
1st and 2nd story shower pans are visually inspected for leaks, but leaks often do not show except when the shower is in actual use. Determining if shower pans, tubs/shower surrounds are water tight is beyond the scope of this inspection. It is very important to maintain all grouting and caulking at the bath area(s). Water supply valves under sink vanities are not turned during this inspection. In doing so, it may subject the valve to leakage.
CEILING MATERIALS: DRYWALL |
WALL MATERIAL: DRYWALL |
FLOOR COVERING(S): TILE |
IN | NI | R/R | S | M/I | NP | ||
3.0.A | SINK(S) (Including Plumbing) | • | |||||
3.1.A | SINK BASE/CABINETRY/COUNTER TOP | • | |||||
3.2.A | ELECTRICAL (Outlets/ Wall Switches/Fixtures) | • | |||||
3.3.A | TOILET(S)(including plumbing) | • | |||||
3.4.A | SHOWER(S)(including plumbing) | • | |||||
3.5.A | TUB(S)(including plumbing) | • | |||||
3.6.A | SHOWER/TUB ENCLOSURE(S) | • | |||||
3.7.A | CEILINGS | • | |||||
3.8.A | WALLS | • | |||||
3.9.A | FLOORS | • | |||||
3.10.A | DOORS (Representative Number) | • | |||||
3.11.A | WINDOWS (Representative Number) | • | |||||
3.12.A | EXHAUST FAN(S) | • | |||||
3.13.A | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
1st and 2nd story shower pans are visually inspected for leaks, but leaks often do not show except when the shower is in actual use. Determining if shower pans, tubs/shower surrounds are water tight is beyond the scope of this inspection. It is very important to maintain all grouting and caulking at the bath area(s). Water supply valves under sink vanities are not turned during this inspection. In doing so, it may subject the valve to leakage.
CEILING MATERIALS: DRYWALL |
WALL MATERIAL: DRYWALL |
FLOOR COVERING(S): TILE |
IN | NI | R/R | S | M/I | NP | ||
3.0.B | SINK(S) (Including Plumbing) | • | |||||
3.1.B | SINK BASE/CABINETRY/COUNTER TOP | • | |||||
3.2.B | ELECTRICAL (Outlets/ Wall Switches/Fixtures) | • | |||||
3.3.B | TOILET(S)(including plumbing) | • | |||||
3.4.B | SHOWER(S)(including plumbing) | • | |||||
3.5.B | TUB(S)(including plumbing) | • | |||||
3.6.B | SHOWER/TUB ENCLOSURE(S) | • | |||||
3.7.B | CEILINGS | • | |||||
3.8.B | WALLS | • | |||||
3.9.B | FLOORS | • | |||||
3.10.B | DOORS (Representative Number) | • | |||||
3.11.B | WINDOWS (Representative Number) | • | |||||
3.12.B | EXHAUST FAN(S) | • | |||||
3.13.B | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
1st and 2nd story shower pans are visually inspected for leaks, but leaks often do not show except when the shower is in actual use. Determining if shower pans, tubs/shower surrounds are water tight is beyond the scope of this inspection. It is very important to maintain all grouting and caulking at the bath area(s). Water supply valves under sink vanities are not turned during this inspection. In doing so, it may subject the valve to leakage.
CEILING MATERIALS: DRYWALL |
WALL MATERIAL: DRYWALL |
FLOOR COVERING(S): CERAMIC |
IN | NI | R/R | S | M/I | NP | ||
3.0.C | SINK(S) (Including Plumbing) | • | |||||
3.1.C | SINK BASE/CABINETRY/COUNTER TOP | • | |||||
3.2.C | ELECTRICAL (Outlets/ Wall Switches/Fixtures) | • | |||||
3.3.C | TOILET(S)(including plumbing) | • | |||||
3.4.C | SHOWER(S)(including plumbing) | • | |||||
3.5.C | TUB(S)(including plumbing) | • | |||||
3.6.C | SHOWER/TUB ENCLOSURE(S) | • | |||||
3.7.C | CEILINGS | • | |||||
3.8.C | WALLS | • | |||||
3.9.C | FLOORS | • | |||||
3.10.C | DOORS (Representative Number) | • | |||||
3.11.C | WINDOWS (Representative Number) | • | |||||
3.12.C | EXHAUST FAN(S) | • | |||||
3.13.C | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
1st and 2nd story shower pans are visually inspected for leaks, but leaks often do not show except when the shower is in actual use. Determining if shower pans, tubs/shower surrounds are water tight is beyond the scope of this inspection. It is very important to maintain all grouting and caulking at the bath area(s). Water supply valves under sink vanities are not turned during this inspection. In doing so, it may subject the valve to leakage.
CEILING MATERIALS: DRYWALL |
FLOOR COVERING(S): TILE |
IN | NI | R/R | S | M/I | NP | ||
3.0.D | SINK(S) (Including Plumbing) | • | |||||
3.1.D | SINK BASE/CABINETRY/COUNTER TOP | • | |||||
3.2.D | ELECTRICAL (Outlets/ Wall Switches/Fixtures) | • | |||||
3.3.D | TOILET(S)(including plumbing) | • | |||||
3.4.D | SHOWER(S)(including plumbing) | • | |||||
3.5.D | TUB(S)(including plumbing) | • | |||||
3.6.D | SHOWER/TUB ENCLOSURE(S) | • | |||||
3.7.D | CEILINGS | • | |||||
3.8.D | WALLS | • | |||||
3.9.D | FLOORS | • | |||||
3.10.D | DOORS (Representative Number) | • | |||||
3.11.D | WINDOWS (Representative Number) | • | |||||
3.12.D | EXHAUST FAN(S) | • | |||||
3.13.D | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
A visual inspection only is performed at the laundry area(s). Appliances are not moved, operated or inspected. Plumbing is visually inspected, gas lines and 220 Volt outlets are not tested. The condition of the floors or walls behind appliances cannot be determined. Drain lines and water supply valves serving the plumbing are not operated. Water supply valves may be subject to leakage if turned.
LOCATION: SEPERATE LAUNDRY ROOM |
GAS SERVICE AVAILABLE: YES |
220 VOLT SERVICE AVAILABLE: NO |
DRYER POWER SOURCE: NATURAL GAS |
IN | NI | R/R | S | M/I | NP | ||
4.0 | LOCATION | • | |||||
4.1 | PLUMBING | • | |||||
4.2 | ELECTRICAL | • | • | ||||
4.3 | GAS SERVICE | • | |||||
4.4 | DRYER VENTING | • | |||||
4.5 | CABINETS / COUNTER TOPS | • | |||||
4.6 | CEILING | • | |||||
4.7 | WALLS | • | |||||
4.8 | FLOORING | • | |||||
4.9 | DOOR(S) | • | |||||
4.10 | EXHAUST FAN | • | |||||
4.11 | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
GARAGE DOOR TYPE: THREE CAR AUTOMATIC ATTACHED |
GARAGE DOOR MATERIAL: ROLL UP |
OPENER MANUFACTURER: ANAHEIM DOOR |
GARAGE FLOOR MATERIAL: CONCRETE PAINTED |
IN | NI | R/R | S | M/I | NP | ||
5.0 | GARAGE DOOR OPERATORS | • | |||||
5.1 | CONDITION OF GARAGE DOOR(S) | • | |||||
5.2 | PEDESTRIAN DOOR(S) | • | |||||
5.3 | ELECTRICAL | • | |||||
5.4 | CEILINGS (including firewall protection) | • | |||||
5.5 | WALLS (including firewall protection) | • | |||||
5.6 | FLOORS | • | |||||
5.7 | WINDOWS (Representative Number) | • | |||||
5.8 | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
The attic is inspected from the visible and accessible area(s) only. The Inspector does not move attic insulation for the inspection. The inspector does not inspect for or determine the "R" factor of the insulation. It is recommended for energy efficiency to have your local heating/cooling utility provider inspect the attic insulation.
ATTIC INFO: SCUTTLE HOLE |
METHOD USED TO OBSERVE ATTIC: FROM ENTRY |
ROOF STRUCTURE: MANUFACTURED TRUSS |
SHEATHING TYPE: OSB BOARD |
ATTIC INSULATION: FIBERGLASS R-FACTOR IS UNKNOWN |
VENTILATION: ADEQUATE |
IN | NI | R/R | S | M/I | NP | ||
6.0 | ATTIC ACCESS | • | |||||
6.1 | ATTIC INSULATION (Coverage) | • | |||||
6.2 | VENTILATION OF ATTIC | • | |||||
6.3 | ROOF STRUCTURE AND ATTIC FRAMING | • | |||||
6.4 | VISIBLE ELECTRICAL WIRING | • | |||||
6.5 | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
SIDING MATERIAL: STUCCO STONE VENEER and |
EXTERIOR ENTRY DOORS: SERVICABLE |
WALKWAY(S): CONCRETE |
DRIVEWAY: CONCRETE |
FENCING/GATES: BLOCK WALLS WROUGHT IRON and |
IN | NI | R/R | S | M/I | NP | ||
7.0 | EAVES, SOFFITS AND FASCIAS | • | |||||
7.1 | EXTERIOR WALL COVERING, FLASHING AND TRIM | • | |||||
7.2 | WINDOWS (Exterior) | • | |||||
7.3 | DOORS (Exterior) | • | |||||
7.4 | ELECTRICAL (Outlet(s) / Switches / Fixtures) | • | |||||
7.5 | DECKS, BALCONIES, STEPS, PORCHES, PATIO COVER(S) AND APPLICABLE RAILINGS | • | |||||
7.6 | DRIVEWAY, WALKWAY(S), PATIO SLAB(S), STOOP(S) | • | |||||
7.7 | FENCING / GATE(S) | • | |||||
7.8 | LANDSCAPING, GRADING, DRAINAGE (Excluding Irrigation System) | • | |||||
7.9 | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
UTILITY SERVICE: WATER IS ON |
PLUMBING SUPPLY: COPPER |
PLUMBING DISTRIBUTION: COPPER |
PLUMBING WASTE: ABS VISIBILITY IS LIMITED |
LOCATION OF WATER HEATER: GARAGE |
CAPACITY: 50 GALLONS |
MANUFACTURER: RHEEM |
YEAR OF MANUFACTURE: 2010 |
WATER HEATER POWER SOURCE: NATURAL GAS |
IN | NI | R/R | S | M/I | NP | ||
8.0 | HOT WATER HEATER(S), CONTROLS, FLUES AND VENTS | • | |||||
8.1 | HOT WATER HEATER SEISMIC STRAPPING | • | |||||
8.2 | GAS SUPPLY (Where Applicable) | • | |||||
8.3 | VISIBLE PLUMBING LINES | • | |||||
8.4 | HOSE FAUCET CONNECTION(S) | • | |||||
8.5 | WATER PRESSURE AT HOSE CONNECTION | • | |||||
8.6 | MAIN WATER SHUT-OFF (Location / Condition) | • | |||||
8.7 | MISCELLANEOUS | • | • | ||||
IN | NI | R/R | S | M/I | NP |
NOTE: Asbestos materials have been commonly used in heating systems. Determining the presence of asbestos can ONLY be determined by laboratory testing and is beyond the scope of this inspection.
GAS SUPPLY: ON |
LOCATION OF PRIMARY UNIT: ATTIC CEILING UNIT and |
HEAT TYPE: FORCED AIR UNIT (FAU) HEAT PUMP (FORCED AIR) and |
ENERGY SOURCE: NATURAL GAS WATER/ELECTRIC and |
NUMBER OF HEAT SYSTEMS: TWO |
MANUFACTURER: CARRIER FIRST CO. and |
YEAR OF MANUFACTURE: SAME AS DWELLING |
FILTER TYPE: DISPOSABLE |
DUCTWORK: FLEXIBLE ROUND And INSULATED |
TYPES OF FIREPLACES: GAS |
IN | NI | R/R | S | M/I | NP | ||
9.0 | HEATING EQUIPMENT | • | |||||
9.1 | LOCATION OF PRIMARY UNIT | • | |||||
9.2 | GAS SUPPLY (Where Applicable) | • | |||||
9.3 | NORMAL OPERATING CONTROLS | • | |||||
9.4 | FILTRATION | • | |||||
9.5 | FLUES AND VENTS (For Furnace) | • | |||||
9.6 | DUCT AIR SUPPLY | • | |||||
9.7 | AIR PLENUM | • | |||||
9.8 | FIREPLACE(S) | • | |||||
9.9 | GAS METER | • | |||||
9.10 | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
MANUFACTURER: CARRIER |
YEAR OF MANUFACTURE: APPEARS SAME AS DWELLING |
COOLING EQUIPMENT TYPE: CENTRAL AIR CONDITION UNIT |
NUMBER OF A/C UNITS: TWO |
IN | NI | R/R | S | M/I | NP | ||
10.0 | COOLING AND AIR HANDLER EQUIPMENT | • | |||||
10.1 | NORMAL OPERATING CONTROLS | • | |||||
10.2 | RETURN AIR TEMPERATURE DROP | • | |||||
10.3 | CONDENSATION LINE | • | |||||
10.4 | ELECTRICAL | • | |||||
10.5 | PROPER AIR CIRCULATION CLEARANCE AT CONDENSER | • | |||||
10.6 | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
The inspector shall observe: Service entrance conductors; service equipment, grounding equipment, main over current device, and main and distribution panels; amperage and voltage ratings of the service; branch circuit conductors, their over current devices, and the compatibility of their ampacities and voltages; the operation of a representative number of installed ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage, and on the dwelling's exterior walls; The polarity and grounding of various receptacles within six feet of interior plumbing fixtures, and various receptacles in the garage or carport, and on the exterior of inspected structures; The operation of ground fault circuit interrupters; and smoke detectors. The inspector shall describe: Service amperage and voltage; service entry conductor materials; service type as being overhead or underground; and location of main and distribution panels. The inspector shall report any observed aluminum branch circuit wiring. The inspector shall report on presence or absence of smoke detectors, and operate their test function, if accessible, except when detectors are part of a central system. The inspector is not required to: Insert any tool, probe, or testing device inside the panels; test or operate any over current device except ground fault circuit interrupters; dismantle any electrical device or control other than to remove the covers of the main and auxiliary distribution panels; or Observe: Low voltage systems; including landscape lighting, security system devices, heat detectors, or carbon monoxide detectors; telephone, security, cable TV, intercoms, or other ancillary wiring that is not a part of the primary electrical distribution system; or built-in vacuum equipment.
Any electrical repairs attempted by anyone other than a licensed electrician should be approached with caution.
Aluminum wiring requires periodic inspection and maintenance by a qualified electrician due to the heating and cooling effects.
UTILTY STATUS: ELECTRIC IS ON |
PANEL TYPE: CIRCUIT BREAKERS |
PANEL CAPACITY: 200 AMP |
SERVICE ENTRANCE CONDUCTORS: BELOW GROUND |
BRANCH WIRE: COPPER |
MANUFACTURE: SQUARE D |
LOCATION OF SERVICE PANEL: LEFT SIDE, FACING STRUCTURE |
IN | NI | R/R | S | M/I | NP | ||
11.0 | LOCATION OF SERVICE PANEL(S) | • | |||||
11.1 | CIRCUIT BREAKERS OR FUSES INSIDE PANEL | • | |||||
11.2 | VISIBLE WIRING AT SERVICE PANEL | • | |||||
11.3 | CLEARANCE AROUND SERVICE PANEL | • | |||||
11.4 | SERVICE ENTRANCE CONDUCTORS | • | |||||
11.5 | SERVICE AND GROUNDING EQUIPMENT | • | |||||
11.6 | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
VIEWED ROOF COVERING FROM: LADDER GROUND and |
ROOF COVERING: TILE |
ROOF STYLE: HIP & VALLEY |
IN | NI | R/R | S | M/I | NP | ||
12.0 | ROOF COVERINGS | • | • | ||||
12.1 | EXPOSED FLASHINGS | • | |||||
12.2 | ROOF PENETRATIONS | • | |||||
12.3 | GUTTER SYSTEM | • | |||||
12.4 | CHIMNEY(S) | • | |||||
12.5 | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
THIS IS AN OPERATIONAL INSPECTION OF THE ITEMS LISTED AND NOT A CERTIFICATION OF ANY SORT. THIS POOL/SPA REPORT IS A VISUAL INSPECTION AND OPERATIONAL TESTOF THE ABOVE GROUND EQUIPMENT ONLY.INSPECTION OF POOL/SPA SURFACE OR CONSEALED COMPONENTS ARE NOT WITHIN THE SCOPE OF THIS REPORT. CLIENT IS ADVISED TO CONSULT WITH AN APPROPRIATE SPECIALIST IF CONCERNED BY THE CONDITIONS IDENTIFIED IN THIS INSPECTION AND REPORT OR WHICH THEY MAY HAVE OBSERVED.
STYLE: IN GROUND & HEATED |
WALL MATERIALS: PEBBLE COAT |
WATER SYSTEM: SALT WATER |
HEATER: PENTAIR |
IN | NI | R/R | S | M/I | NP | ||
13.0 | SURFACE WALLS AND FLOOR OF POOL/SPA | • | |||||
13.1 | DECKING | • | |||||
13.2 | COPING | • | |||||
13.3 | PUMPS FOR CIRCULATION OF WATER | • | |||||
13.4 | OPERATIONAL CONDITION OF POOL/SPA | • | |||||
13.5 | FILTRATION/SKIMMER | • | |||||
13.6 | POOL/SPA HEATERS | • | |||||
13.7 | LIGHTING (Pool/Spa) | • | |||||
13.8 | ELECTRICAL | • | |||||
13.9 | SAFETY EQUIPMENT | • | |||||
13.10 | MISCELLANEOUS | • | |||||
IN | NI | R/R | S | M/I | NP |
![]() |
INVOICE |
1st Choice Property Inspections
20432 Alcalde Ste D Laguna Hills, Ca 92653 949.413.3650 Cell 888.202.4642 Office email: youroneinspector@gmail.com www.1stchoicepropertyinspections.net Inspected By: Gregg Traum |
Inspection Date: 12/8/2015
Report ID: 15-6051 |
Customer Info: | Inspection Property: |
Jim Shoe
Customer's Real Estate Professional: Joe Realtor ABC Realty |
10 Portalon Ladera Ranch Ca 92694 |
Inspection Fee:
| ||||||||||||
Tax $0.00 | ||||||||||||
Total Price $475.00 |
Payment Method: Check
Payment Status: Paid At Time Of Inspection
Note: THANK YOU FOR YOUR BUSINESS!!